• <noscript id="4m06m"></noscript>
  • 0512-67541361

    High Voltage Switchgear Equipment

    Current Location:Home > Product > High Voltage Switchgear Equipment

    KYN28A-12 type armoured transfer type AC metal closed switchgear

    KYN28A-12 armored transfer type AC metal closed switch equipment is a three-phase AC rated voltage 12kV, rated frequency 50HZ complete set of distribution equipment. It is mainly used in the transformation of power plants, substations, industrial and mining enterprises and high-rise buildings as a way to receive and distribute electric energy, so as to control, protect and monitor. This switchgear meets the standards of GB3906, GB11022 and IEC298 (1009).

    ◇Main features:

    The switchgear is made up of two parts, the cabinet and the removable parts. The appearance is flat, simple and beautiful. It has a simple and reliable "five guard" interlocking function, which prevents misoperation.

    The two line grooves in high pressure indoor use all metal protection, and the operation is safer and more reliable.

    The heater can be installed separately in the circuit breaker room and the cable room to prevent condensation and corrosion.

    All devices are properly equipped with the same place for inspection.

    When a substation is designed to form a complete set of equipment with various functions, it needs less space and can be applied to any premises inside and outside the house.

    According to customer needs, it is easy to fit the structure, and easy to install and locate in any floor.

    The charged part is properly insulated, and all the components are installed in the metal box, which is very safe for the personnel or equipment. When using a complete set of substations, the high voltage circuit is easy to penetrate into the load center and reduce the power loss, and the voltage can be improved.


    ◇Technical parameters:

    Serial number

    Name

    Company

    numerical value

    1

    Rated voltage

    kV

    12

    2

    Rated current

     A 

    630  1250  1600  2000  2500  3150  4000

    3

    Rated frequency

     Hz 

    50

    4

    1min power frequency tolerance voltage phase, relative ground

    kV

    42

    5

    1min power frequency tolerance voltage isolation (fracture)

    kV

    48

    6

    Lightning impulse tolerance voltage peak

    Interphase, relative

    kV

    75

    7

    Lightning impulse tolerance voltage peak

    (fracture)

    kV

    85

    8

    The main busbar rated current

    A

    630  1250  1600  2000  2500  3150  4000

    9

    Branch bus rated current

     A 

    630  1250  1600  2000  2500  3150   4000

    10

    Rated short circuit breaking current

     kA 

    20  25  31.5  40 

    11

    Rated short-time tolerance current / rated short duration

     kA/4S 

    20  25  31.5  40 

    12

    Rated peak tolerance current

     kA 

    50  63  80  100 

    13

    Rated short-circuit closing current

     kA 

    50  63  80  100 

    14

    1min auxiliary circuit power frequency tolerance voltage

     V 

    2000

    15

    Protection grade

     

    IP4X (open door opening of circuit breaker or IP2X between compartments)


    ◇Product size:

    nucha

    width(mm)

    height(mm)

    depth(mm)

    KYN28A-12

    650、800、1000

     2320

       1510、1670、1810

    Support By:Youba INC.